PoE Budget
IEEE 802.3af / at / bt · NEC 725 · NEC 800 · ANSI/BICSI 007-2024 · ASHRAE thermal guidelines
Capacity and layout
The drawing appears when the inputs are complete
- 01Budget Power over Ethernet across a switch: per-class draw for 802.3af/at/bt Types 1–4, cable-length loss, PSU redundancy, simultaneity and headroom.
- 02Tip. Budget against the class the switch reserves, not the wattage the device actually draws. A switch allocates the full class to every powered port at negotiation, so a rack of devices sitting at half their class can still exhaust the supply on paper and refuse to power the next one.
- 0315.4 W — Type 1 at the PSE
- 0430 W — Type 2 (802.3at)
- 0560 W — Type 3 (802.3bt)
- 0690 W — Type 4 (802.3bt)
- 07100 m — Maximum channel
IEEE 802.3 Power over Ethernet
PoE budgeting has two figures that are easy to confuse. The PSE figure is what the switch must supply and reserve for a port; the PD figure is what the device can actually draw at the far end. The difference between them is the loss allowed in the channel, and it is why cable length and category belong in a power calculation at all.
Types and classes
Each type sets a maximum at the switch and a guaranteed minimum at the device. Types 1 and 2 power two pairs; Types 3 and 4 use all four, roughly halving the channel resistance.
Use cases
- Type 1 (802.3af) — 15.4 W PSE, 12.95 W PD
- Type 2 (802.3at) — 30 W PSE, 25.5 W PD
- Type 3 (802.3bt) — 60 W PSE, 51 W PD
- Type 4 (802.3bt) — 90 W PSE, 71.3 W PD
Formula
Channel loss = I²R, where I = PD watts ÷ bus voltage
IEEE 802.3af / at / bt
Budget and headroom
A switch reserves the full class for every powered port at negotiation, whatever the device actually draws. Budget on class, then add headroom and check the supply redundancy.
Use cases
- Sum class allocations, not measured draw
- Add the switch’s own base consumption
- Simultaneity — will everything draw at once
- Headroom for growth, typically 20 %
Formula
Supply = Σ(class W) × simultaneity × (1 + headroom) + switch base
100 m maximum channel
Cable resistance is the reason a 90 m run behaves differently from a 5 m one. Thinner conductors and longer channels dissipate more of the supplied power as heat before it reaches the device, which is why Cat 5e at full length can fail to deliver a load that Cat 6A carries comfortably.
- 01PoE classes and budgets — IEEE 802.3af / at / bt
- 02Class 2 and Class 3 circuits — NEC 725
- 03Communications circuits — NEC 800
- 04ICT design for intelligent buildings — ANSI/BICSI 007-2024
- 05Equipment room cooling — ASHRAE thermal guidelines